Trustworthy good quality and excellent credit score standing are our principles, which will help us at a good -ranking position. Adhering towards the tenet of quality first, buyer supreme for
Ultrafiltration Water System
, Micro Filtration
, Membrane Microfilter
, We sincerely welcome customers from both at home and abroad to come to negotiate business with us.
Chinese Professional Water Treatment Systems -
UF Membrane Module PVC Ultrafiltration Membrane Module UFc4040 RO housing – Bangmo Detail:
Applications
Production of mineral water, spring water, or other sterile liquid.
Drinking treatment of tap water, surface water, well water and river water.
Pretreatment of RO.
Treatment, recycle and reuse of industrial waste water.
Filtration Performance
This product is proven to have below filtering effects according to the service?conditions of different water sources:
Ingredient |
Effect |
SS, Particles?> 1μm |
Removal Rate?≥ 99% |
SDI |
≤ 3 |
Bacteria, Viruses |
>?4 log |
Turbidity |
<0. 1NTU |
TOC |
Removal Rate: 0-25% |
*Above data is obtained under the condition that feeding water turbidity is < 15NTU. This product is qualified for drinking water related products.
Product Parameters

Technical Parameters
Filtering?Type |
Inside-out |
Membrane?Material |
Modified?PVC |
MWCO |
100K Dalton |
Membrane?Area |
3.8m2 |
Membrane?ID/OD |
1.0mm/1.8mm |
Dimensions |
Φ90mm*1016mm |
Connector?Size |
Φ19mm |
Application Data
Pure?Water?Flux |
1,200L/H?(0.15MPa, 25C) |
Designed?Flux |
35-100L/m2.hr?(0.15MPa, 25C) |
Suggested?Working?Pressure |
≤ 0.2MPa |
Maximum?Transmembrane?Pressure |
0.2MPa |
Maximum?Working?Temperature |
45C |
PH?Range |
Working: 4-10; Washing: 2-12 |
Operating?Mode |
Cross-flow?or?Dead-end |
Feeding Water Requirements
Before feeding water, a security filter < 50 μm should be set to prevent blockage caused?by large particles in raw water.
Turbidity |
≤ 15NTU |
Oil?&?Grease |
≤?2mg/L |
SS |
≤ 20mg/L |
Total?Iron |
≤?1mg/L |
Continuous?Residual?Chlorine |
≤?5ppm |
COD |
Suggested?≤ 500mg/L |
*Material of UF membrane is polymer organic plastic, there must not be any organic solvents in raw water.
Operating Parameters
Maximum?Backwashing?Pressure |
0.2MPa |
Backwashing?Flow?Rate |
100-150L/m2.hr |
Backwashing?Frequency |
Every?30-60min. |
Backwashing?Duration |
30-60s |
CEB?Frequency |
0-4?times per day |
CEB?Duration |
5-10min. |
CIP?Frequency |
Every 1-3 months |
Washing?Chemicals: |
Sterilization |
15ppm Sodium Hypochlorite |
Organic?Pollution?Washing |
0.2%?Sodium Hypochlorite + 0.1% Sodium Hydroxide |
Inorganic?Pollution?Washing |
1-2% Citric?Acid/0.2% Hydrochloric?Acid |
Component Material
Component |
Material |
Membrane |
Modified?PVC |
Sealing |
Epoxy?Resins |
Housing |
UPVC |
Product detail pictures:
Related Product Guide:
Our progress depends around the innovative machines, great talents and consistently strengthened technology forces for
Chinese Professional Water Treatment Systems -
UF Membrane Module PVC Ultrafiltration Membrane Module UFc4040 RO housing – Bangmo , The product will supply to all over the world, such as: United Arab Emirates
, Mexico
, St. Petersburg
, Our products are exported worldwide. Our customers are always satisfied with our reliable quality, customer-oriented services and competitive prices. Our mission is to continue to earn your loyalty by dedicating our efforts to the constant improvement of our products and services in order to ensure the satisfaction of our end-users, customers, employees, suppliers and the worldwide communities in which we cooperate.